2.6 Basic commissioning

Complete the basic commissioning as follows before the actual use of the VFD:
According to the actual motor parameters, select the motor type, set motor parameters,
and select the VFD control mode.
Autotune. If possible, de-couple the VFD from the motor load to start dynamic
autotuning. If the VFD cannot be de-coupled from the load, perform static autotuning.
Adjust the ACC/DEC time according to the actual work condition of the load.
Perform device commissioning by means of jogging and check whether the motor
rotational direction is correct. If not, change the rotation direction by swapping any
two phase wires of the motor.
Set all control parameters and then operate.