Kruger Ecowatt K320 Series Operation Manual page 198

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
VFD input power
P08.51
factor
P08.52 STO lock selection
Upper limit
frequency bias
P08.53
value in torque
control
Upper limit
frequency
P08.54
ACC/DEC selection
in torque control
P09 group–– PID control
Function
Name
code
PID reference
P09.00
source
Description
during magnetic flux braking, while the
cooling of the stator is more effective
than the rotor.
The function code is used to adjust the
display value on the AC input side.
0.00–1.00
0: Lock upon STO alarm
Lock upon STO alarm indicates resetting
is required after state restoration if STO
occurs.
1: No lock on STO alarm
No lock on STO alarm indicates STO
alarm disappears automatically after
state restoration if STO occurs.
0.00 Hz–P00.03 (Max. output frequency)
Note: Valid only for torque control.
0:
No
limit
on
deceleration
1: ACC/DEC time 1
2: ACC/DEC time 2
3: ACC/DEC time 3
4: ACC/DEC time 4
Description
When the frequency command selection
(P00.06, P00.07) is 7 or the voltage setting
channel selection ((P04.27) is 6, the VFD is
process PID controlled.
The function code determines the target
given channel during the PID process.
0: Keypad (P09.01)
1: AI1
2: AI2
3: AI3
-189-
Function parameter list
acceleration
or
Default
Modify
0.56
0
0.00Hz
0
Default Modify
0