Kruger Ecowatt K320 Series Operation Manual page 230

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Terminal output
P19.07
status of
expansion I/O card
HDI3 input
P19.08
frequency of
expansion I/O card
AI3 input voltage
P19.09
of expansion I/O
card
P19.10–
Reserved
P19.39
P20 group––Encoder of motor 1
Function
Name
code
Encoder type
P20.00
display
Encoder pulse
P20.01
number
P20.02
Encoder direction
Detection time of
P20.03
encoder offline
fault
Detection time of
P20.04
encoder reversal
fault
Description
0–0xFFFF
0.000–50.000kHz
0.00–10.00V
Description
0: Incremental encoder
1: Resolver-type encoder
2: Sin/Cos encoder
3: Endat absolute encoder
Number of pulses generated when the
encoder revolves for one circle.
Setting range: 0–60000
Ones place: AB direction
0: Forward
1: Reverse
Tens place: Z pulse direction (reserved)
0: Forward
1: Reverse
Hundreds: CD/UVW pole signal direction
0: Forward
1: Reverse
Detection time of encoder offline fault.
Setting range: 0.0–10.0s
Detection time of encoder reversal fault.
Setting range: 0.0–100.0s
-221-
Function parameter list
Default Modify
0
0.000
kHz
0.00V
Default Modify
0
1024
0x000
2.0s
0.8s

Advertisement

Table of Contents
loading

Table of Contents