Kruger Ecowatt K320 Series Operation Manual page 216

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
Initial pole
P13.01
detection method
P13.02
Pull-in current 1
P13.03
Pull-in current 2
Pull-in current
P13.04
switchover
frequency
P13.05
Reserved
Pulse current
P13.06
setting
P13.07
Reserved
Control parameter
P13.08
Control parameter
P13.09
0: Invalid
1: Pulse detection method
2: Pulse detection method
Pull-in current is the pole positioning
current. Pull-in current 1 is valid within
the
lower
switchover frequency threshold. If you
need to increase the starting torque,
increase the value of the function code
properly.
Setting range: 0.0%–100.0% (of the motor
rated current)
Pull-in current is the pole positioning
current. Pull-in current 2 is valid within
the
upper
switchover
Generally, you do not need to modify the
function code.
Setting range: 0.0%–100.0% (of the motor
rated current)
0.00Hz–P00.03 (Max. output frequency)
Used to set the pulse current threshold
when the initial magnetic pole position is
detected by means of pulse. The value is a
percentage in relative to the rated current
of the motor.
Setting range: 0.0–300.0% (of the motor
rated voltage)
0–0xFFFF
1
Used to set the frequency threshold for
enabling the counter-electromotive force
2
phase-locked loop in SVC 0. When the
Description
limit
of
pull-in
limit
of
pull-in
frequency
-207-
Function parameter list
Default Modify
0
current
20.0%
current
threshold.
10.0%
10.00Hz
100.0%
0
2.00