Main Circuit Standard Wiring; Main Circuit Wiring Diagram - Kruger Ecowatt K320 Series Operation Manual

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®

4.3 Main circuit standard wiring

4.3.1 Main circuit wiring diagram

3PH power
380V(-15%)-440V(+10%)
50/60Hz
3PH power
380V(-15%)-440V(+10%)
50/60Hz
3PH power
380V(-15%)-440V(+10%)
50/60Hz
Note:
The fuse, DC reactor, braking unit, braking resistor, input reactor, input filter, output
reactor and output filter are optional parts. See Appendix D Optional peripheral
accessories.
P1 and (+) have been short connected by default for 160P and higher models. If you need to
connect to external DC reactor, take off the short-contact tag of P1 and (+).
When connecting the braking resistor, take off the yellow warning sign marked with PB,
(+) and (-) on the terminal block before connecting the braking resistor wire, otherwise,
poor contact may occur.
Braking units are optional parts for 055P–075P models, and they can be built in or
externally connected to the models.
Braking resistor
R
Input
reactor
045P and lower models
S
Input
filter
T
Fuse
(+)
R
Input
055P–132P models
reactor
S
Input
filter
T
Fuse
DC reactor
(+)
P1
R
Input
reactor
160P and higher models
S
Input
filter
T
Fuse
Figure 4-7 Main circuit wiring diagram
-21-
(+)
(-)
PB
U
V
W
PE
Braking unit
DC+
Braking resistor
DC-
(-)
U
V
W
PE
Braking unit
DC+
Braking resistor
DC-
(-)
U
V
W
PE
Installation guidelines
Output
reactor
M
Output
filter
Output
reactor
M
Output
filter
Output
reactor
M
Output
filter

Advertisement