Kruger Ecowatt K320 Series Operation Manual page 328

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
A.6.5 PROFINET communication card——EC-TX509
The terminal CN2 adopts a standard RJ45 interface, where CN2 is the dual RJ45 interface, and
these two RJ45 interfaces are not distinguished from each other and can be interchangeably
inserted. They are arranged as follows:
Pin
1
2
3
4
5
6
7
8
Indicator definition:
The PROFINET communication card has 9 indicators, of which LED1 is the power indicator,
LED2–5 are the communication state indicators of the communication card, and LED6–9 are
the state indicators of the network port.
LED
LED1
LED2
(Bus state indicator)
LED3
(System fault indicator)
LED4
(Slave ready indicator)
Name
TX+
TX-
RX+
n/c
n/c
RX-
n/c
n/c
Color
State
Green
On
Blinking
Red
Off
On
Green
Off
On
Green
Blinking
Off
-319-
Description
Transmit Data+
Transmit Data-
Receive Data+
Not connected
Not connected
Receive Data-
Not connected
Not connected
Description
3.3V power indicator
No network connection
The connection to the network cable
between the Profinet controller is OK,
but the communication is not
established.
Communication with the Profinet
controller has been established
Profinet diagnosis exists
No Profinet diagnosis
TPS-1 protocol stack has started
TPS-1 waits for MCU initialization
TPS-1 protocol stack does not start
Expansion cards

Advertisement

Table of Contents
loading

Table of Contents