Ecowatt
Drive K320 series
®
Function
code
P06.17
AO1 output lower limit
AO1 output corresponding
P06.18
P06.19
AO1 output upper limit
AO1 output corresponding
P06.20
P06.21
AO1 output filter time
P06.22–
P06.26
P06.27
HDO output lower limit
HDO output corresponding
P06.28
P06.29
HDO output upper limit
HDO output corresponding
P06.30
P06.31
HDO output filter time

5.5.11 Digital input

The VFD provides four programmable digital input terminals and two HDI input terminals. All
the digital input terminal functions can be programmed by function codes. HDI input terminal
can be set to act as high-speed pulse input terminal or common digital input terminal; if it is
set to act as high-speed pulse input terminal, you can also set HDIA or HDIB high-speed pulse
input to serve as the frequency reference and encoder signal input.
Name
to lower limit
to upper limit
Reserved
to lower limit
to upper limit
Description
output frequency)
25: Ramp reference frequency (bipolar,
0–Max. output frequency)
26: Rotational speed (bipolar, 0–Speed
corresponding
to
frequency)
27:
Value
2
EtherCat/Profinet/EtherNetIP (0–1000)
28: C_AO1 (Set P27.00 to 1. 0–1000)
29: C_AO2 (Set P27.00 to 1. 0–1000)
30: Rotational speed (0–Twice the
motor rated synchronous speed)
31:
Output
torque
0–Twice the motor rated torque)
32–47: Reserved
-300.0%–P06.19
0.00V–10.00V
P06.17–300.0%
0.00V–10.00V
0.000s–10.000s
0–65535
-300.0%–P06.29
0.00–50.00kHz
P06.27–300.0%
0.00–50.00kHz
0.000s–10.000s
-94-
Basic operation guidelines
Default
max.
output
set
through
(Actual
value,
100.0%
10.00V
0.000s
0.0kHz
100.0%
50.00kHz
0.000s
0.0%
0.00V
0
0.0%