If the operation is successful, the following response is returned:
address
Example 2: Set "ACC time" of the VFD whose address is 01H to 10s, and "DEC time" to 20s.
Function
Name
code
P00.11
ACC time 1
P00.12
DEC time 1
The address of P00.11 is 000B, 10s is 0064H in the hexadecimal form, and 20s is 00C8H in the
hexadecimal form.
The command transmitted by the master is as follows:
01
10
Continuous
VFD
address
write
command
If the operation is successful, the following response is returned:
01
VFD
address
Note: In the preceding command description, spaces are added to a command just for
explanatory purposes. In practical applications, no space is required in the commands.
9.4.8.4 Modbus communication commissioning example
A PC is used as the host, an RS232-RS485 converter is used for signal conversion, and the PC
serial port used by the converter is COM1 (an RS232 port). The upper computer commissioning
software is the serial port commissioning assistant Commix, which can be downloaded from
the Internet. Download a version that can automatically execute the CRC check function. The
following figure shows the interface of Commix.
01
10
Continuous
VFD
write
command
Setting
range
0.0–3600.0s
00 0B
00 02
Parameter
Parameter
address
quantity
10
00 0B
Continuous
Parameter
write
command
20 00
00 02
Parameter
Parameter
address
quantity
Description
of
P00.11
and
04
Number of
bytes
00 02
Parameter
address
quantity
-297-
4A 08
CRC
Default
Model
depended
P00.12:
Model
depended
00 64
00 C8
20s
10s
30 0A
CRC
Communication
Modify
F2 55
CRC