Function
Name
code
Speed/torque
mode switching
P28.05
frequency point in
master/slave
mode 2
P28.06
Slave count
P28.07–
Reserved
P28.24
Fire mode
P28.25
function
Running
P28.26
frequency in fire
mode
P28.27
Fire mode flag
P28.28–
Reserved
P28.29
Description
0.00–10.00Hz
0–15
0: Invalid
1: Fire mode 1
2: Fire mode 2
When P90.00=0, the fire mode is invalid,
and the normal running mode is used. In
this
case,
the
encountering a fault. When the fire mode
is valid, the VFD runs at the speed
specified by P90.01.
When fire mode 1 is selected, the VFD runs
always except when the VFD has been
damaged.
When fire mode 2 is selected, the VFD runs
always,
but
the
encountering OUT1, OUT2, OUT3, OC1, OC2,
OC3, OV1, OV2, OV3, or SPO.
Note: Terminal control must be used for a
fire mode.
0.00Hz–P00.03 (Max. output frequency)
0–1
When the fire mode has lasted 5 minutes,
it is reset, and no warranty of repair is
processed.
-247-
Function parameter list
VFD
stops
when
VFD
stops
when
Default Modify
5.00Hz
1
0
50.00Hz
0