Kruger Ecowatt K320 Series Operation Manual page 320

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Category
AO2—GND
S5—COM
S6—COM
S7—COM
Digital
S8—COM
input/output
Y2—CME
Relay output
A.5 Programmable expansion card——EC-PC502-00
The terminals are arranged as follows:
SW1 is the start/stop switch of the programmable expansion card. CN1 contains terminals PE,
485-, 485+, GND, AI1, and AO1, and a selection jumper resides on the next. "AI" and "AV" are the
current type input selection and voltage type input selection of AI1, and they can be selected
through J2. "AIO" and "AVO" are the current type output selection and voltage type output
selection of AO1, and they can be selected through J5. "120" indicates
and it can connect to J1. By default, J1 connects to NC, J2 to AV, and J5 to AVO.
Sign
Name
Analog output 1
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital output
RO3A
NO contact of relay 3
RO3B
NC contact of relay 3
Common contact of
RO3C
relay 3
RO4A
NO contact of relay 4
Common contact of
RO4C
relay 4
1. Output range: 0–10 V, 0–20 mA
2. Whether it is voltage or current output
is determined by J5.
3. Deviation ±0.5%; input of 5 V or 10 mA or
higher at the temperature of 25°C
1. Internal impedance: 3.3 kΩ
2. Power input range: 12–30 V
3. Bidirectional input terminal
4. Max. input frequency: 1 kHz
1. Switch capacity: 200 mA/30 V
2. Output frequency range: 0–1 kHz
3. The terminals CME and COM are
shorted through J3 before delivery.
1. Contact capacity: 3A/AC 250 V, 1 A/DC
30 V
2. Do not use them as high-frequency
digital outputs.
-311-
Expansion cards
Function
120Ω
terminal resistor,

Advertisement