A. Vertical installation

4.2.3 Installation mode

There are three kinds of installation modes based on different VFD dimensions.
Wall-mounting: suitable for 355P and lower models
Flange-mounting: suitable for 220P and lower models
Floor-mounting: suitable for 250P–500P models
(1) Mark the position of the installation hole. See appendix for the position of installation hole;
(2) Mount the screws or bolts onto the designated position;
(3) Put the VFD on the wall;
(4) Tighten the fixing screws on the wall.
Note:
The flange-mounting plate is a must for 2R2P–090P models that adopt flange-mounting
mode; while 110P–220P models need no flange-mounting plate.
The installation base is optional for 250P–355P models. The base can hold an input AC
reactor (or DC reactor) and an output AC reactor.
NG
B. Horizontal installation
Figure 4-1 Installation direction of the VFD
Wall-mounting
Figure 4-2 Installation mode
C. Transverse installation
Flange-mounting
-17-
Installation guidelines
NG