Ecowatt
Drive K320 series
®
Function
Name
code
P08.42
Reserved
P08.43
Reserved
UP/DOWN
terminal control
P08.44
setting
Frequency
increment integral
P08.45
rate of the UP
terminal
Frequency integral
P08.46
rate of the DOWN
terminal
Action selection at
P08.47
power-off during
frequency setting
Description
0x000–0x221
Ones place: Frequency setting selection
0: The setting made through UP/DOWN
is valid.
1: The setting made through UP/DOWN
is invalid.
Ones place: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency setting methods
2: Invalid for multi-step speed running
when multi-step speed running has the
priority
Hundreds place: Action selection for
stop
0: Setting is valid.
1: Valid during running, cleared after
stop
2: Valid during running, cleared after a
stop command is received
0.01–50.00Hz/s
0.01–50.00Hz/s
0x000–0x111
Ones place: Action selection at power-off
during
frequency
digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during
frequency adjusting through Modbus/
Modbus TCP communication
-187-
adjusting
through
Function parameter list
Default
Modify
0x000
0.50Hz/s
0.50Hz/s
0x000