Ecowatt
Drive K320 series
®
Function
Name
code
PID reference
P09.01
preset through
keypad
PID feedback
P09.02
source
Description
4: High-speed pulse HDIA
5: Multi-step running
6: Modbus/Modbus TCP communication
7:
Profibus/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10:
EtherCAT/Profinet/EtherNetIP
communication
11: Programmable expansion card
12: Reserved
The set target of process PID is a relative
value, for which 100% equals 100% of the
feedback signal of the controlled system.
The system always calculates a related
value (0–100.0%).
The function code is mandatory when
P09.00=0. The base value of The function
code is the feedback of the system.
Setting range: -100.0%–100.0%
The function code is used to select PID
feedback channel.
0: AI1
1: AI2
2: AI3
3: HDIA
4: Modbus/Modbus TCP communication
5:
PROFIBUS/CANopen/DevicneNET
communication
6: Ethernet communication
7: HDIB
8:
EtherCat/Profinet/EtherNetIP
communication
9: Programmable expansion card
10: Reserved
Note: The reference channel and feedback
channel cannot be duplicate. Otherwise,
effective PID control cannot be achieved.
-190-
Function parameter list
Default Modify
0.0%
0