If static autotuning is selected for motor autotuning, there is no need to disconnect the
motor from the load, but the control performance may be impacted as only a part of the
motor parameters have been autotuned. In addition, autotune P02.06–P02.10 for AMs and
autotune P02.20–P02.22 for SMs. P02.23 can be obtained through calculation.
Motor autotuning can be carried out on the present motor only. If you need to perform
autotuning on the other motor, switch the motor through selecting the switchover
channel of motor 1 and motor 2 by setting the ones place of P08.31.
Related parameter list:
Function
code
Channel of running
P00.01
Motor parameter
P00.15
P02.00
Type of motor 1
P02.01
Rated power of AM 1 0.1–3000.0kW
Rated frequency of
P02.02
Name
0: Keypad
1: Terminal
commands
2: Communication
0: No operation
1: Rotary autotuning 1.
Comprehensive motor parameter
autotuning. It is recommended to use
rotating autotuning when high control
accuracy is needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in
cases where the motor cannot be
disconnected from load.
autotuning
3: Static autotuning 2 (partial autotuning);
when the present motor is motor 1, only
P02.06, P02.07 and P02.08 are autotuned;
when the present motor is motor 2, only
P12.06, P12.07 and P12.08 are autotuned.
4: Rotary autotuning 2. Similar to rotary
autotuning 1, but it is valid only for AMs.
5: Static autotuning 3 (partial autotuning),
valid only for AMs.
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0.01Hz–P00.03 (Max. output frequency)
AM 1
Description
-75-
Basic operation guidelines
Default
0
0
0
Model
depended
50.00Hz