Kruger Ecowatt K320 Series Operation Manual page 20

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function description
Peripheral
interface
Extended interfaces
Mounting method
Ingress protection
Other
Terminal analog
input resolution
Terminal digital
input resolution
Analog input
Analog output
Digital input
Digital output
Relay output
Temperature of
running
environment
rating
Pollution degree
Cooling method
Braking unit
EMC filter
No more than 20mV
No more than 2ms
2 inputs; AI1: 0–10V/0–20mA; AI2: -10–10V
1 input; AO1: 0–10V/0–20mA
Four regular inputs; max. frequency: 1kHz; internal
impedance: 3.3kΩ
Two high-speed inputs; max. frequency: 50kHz;
supporting quadrature encoder input; with speed
measurement function
One high-speed pulse output; max. frequency: 50kHz
One Y terminal open collector output
Two programmable relay outputs
RO1A: NO; RO1B: NC; RO1C: common
RO2A: NO; RO2B: NC; RO2C: common
Contact capacity: 3A/AC250V, 1A/DC30V
Three extended interfaces: SLOT1, SLOT2, and SLOT3
(control board of above 7.5kW)
Supporting PG cards, programmable expansion cards,
communication cards, I/O cards and so on
Wall mounting, floor mounting, and flange mounting
-10 – +50°C; derating is required if the ambient
temperature exceeds 40°C
IP20
Degree 2
Forced air cooling
The VFD models of 045P and lower contain built-in
braking units. The braking units are optional parts
for the 055P–055/075P VFD models, and the braking
units can be built in or externally connected.
The transmission of the VFD meets the IEC/EN
61800-3 C3 requirements.
When optional filters are connected externally, the
transmission of the VFD can meet the IEC/EN 61800-3
C2 requirements.
Note: Comply with the EMC requirements and the
technical requirements for the motors and motor
cables in the appendix in the manual.
-11-
Product overview
Specification

Advertisement