Ecowatt
Drive K320 series
®
4.2.4 Single-unit installation
A
B
A
Note: The min. dimension of B and C is 100mm.
4.2.5 Multiple-unit installation
A
B
A
Note:
When you install VFDs in different sizes, align the top of each VFD before installation for
the convenience of future maintenance.
The min. dimension of B, D and C is 100mm.
B
Figure 4-3 Single-unit installation
D
B
Figure 4-4 Parallel installation
-18-
Installation guidelines
C
Hot air
Cold air
C
Hot air
C
Cold air
C