Installation Direction - Kruger Ecowatt K320 Series Operation Manual

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Environment
Humidity
Storage
-30–+60°C
temperature
The installation site should meet the following requirements.
Running
environment
Altitude
Vibration
The max. amplitude of vibration should not exceed 5.8m/s
Installation
Install the VFD vertically to ensure good heat dissipation effect
direction
Note:
The VFD must be installed in a clean and well-ventilated environment based on the IP
level.
The cooling air must be clean enough and free from corrosive gases and conductive dust.

4.2.2 Installation direction

The VFD can be installed on the wall or in a cabinet.
The VFD must be installed vertically. Check the installation position according to following
requirements. See Appendix C Dimension drawings.
The relative humidity (RH) of the air is less than 90%;
Condensation is not allowed;
The max RH cannot exceed 60% in the environment where there are
corrosive gases.
Away from electromagnetic radiation sources;
Away from oil mist, corrosive gases and combustible gases;
Ensure foreign object like metal powder, dust, oil and water will not
fall into the VFD (do not install the VFD onto combustible object like
wood);
Away from radioactive substance and combustible objects;
Away from harmful gases and liquids;
Low salt content;
No direct sunlight
Below 1000m;
When the altitude exceeds 1000m, derate 1% for every additional 100m;
When the altitude exceeds 2000m, configure isolation transformer on
the input end of the VFD. It is recommended to keep the altitude below
5000m.
Condition
-16-
Installation guidelines
(0.6g)
2