press the PRG/ESC key to enter the function code editing interface. You need to enter the
correct user password to enter the interface. For the factory parameters, you need to enter the
correct factory password to enter the interface. (You are not advised to modify the factory
parameters. Incorrect parameter setting may cause operation exceptions or even damage to
the VFD.) If password protection is not in locked state, you can change the password any time.
You can set P07.00 to 0 to cancel the user password. When P07.00 is set to a non-zero value
during power-on, parameters are prevented from being modified by using the user password
function. When you modify function parameters through serial communication, the user
password protection function is also applicable and compliant with the same rule.
P00 group––Basic functions
Function
Name
code
Speed control
P00.00
mode
Channel of
P00.01
running
commands
Communication
P00.02
mode of running
commands
Max. output
P00.03
frequency
Description
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
3: Closed-loop vector control mode
Note: To select 0, 1, or 3 as the control
mode, enable the VFD to perform motor
parameter autotuning first.
0: Keypad
1: Terminal
2: Communication
0: Modbus/Modbus TCP
1: Profibus/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/Profinet/EtherNetIP
4: Programmable expansion card
5: Wireless communication card
Note: The options 1, 2, 3, 4, and 5 are
add-on functions and are available only
when corresponding expansion cards are
configured.
Used to set the max. output frequency of
the VFD. Pay attention to the function code
because it is the foundation of the
frequency
setting
acceleration (ACC) and deceleration (DEC)
Setting
range:
10.00)–400.00Hz
-133-
Function parameter list
and the
speed of
Max
(P00.04
Default Modify
2
0
0
50.00Hz