D.8 Braking system
D.8.1 Brake component selection
When the VFD driving a high-inertia load decelerates or needs to decelerate abruptly, the
motor runs in the power generation state and transmits the load-carrying energy to the DC
circuit of the VFD, causing the bus voltage of the VFD to rise. If the bus voltage exceeds a
specific value, the VFD reports an overvoltage fault. To prevent this from happening, you need
to configure brake components.
The design, installation, commissioning, and operation of the device must
be performed by trained and qualified professionals.
Follow all the "Warning" instructions during the operation. Otherwise,
major physical injuries or property loss may be caused.
Only qualified electricians are allowed to perform the wiring. Otherwise,
damage to the VFD or brake components may be caused.
Read the braking resistor or unit instructions carefully before connecting
them to the VFD.
Connect braking resistors only to the terminals PB and (+), and braking
units only to the terminals (+) and (-). Do not connect them to other
terminals. Otherwise, damage to the brake circuit and VFD and fire may
be caused.
Connect the brake components to the VFD according to the wiring
diagram. If the wiring is not properly performed, damage to the VFD or
other devices may be caused.
The VFD models of 045P and lower are equipped with built-in braking units, and those of 055P
and higher need to be configured with external braking units. The VFD models of 055P–075P
can be configured with optional built-in braking units, and after a built-in braking unit is
configured, the VFD model code is added with a suffix "-B", for example, K320-055P-4-B. Select
braking resistors according to the specific requirements (such as the brake torque and brake
usage requirements) on site.