Kruger Ecowatt K320 Series Operation Manual page 165

Variable frequency drive
Hide thumbs Also See for Ecowatt K320 Series:
Table of Contents

Advertisement

Ecowatt
Drive K320 series
®
Function
Name
code
V/F slip
P04.09
compensation
gain of motor 1
Low-frequency
P04.10
oscillation control
factor of motor 1
High-frequency
P04.11
oscillation control
factor of motor 1
Oscillation control
P04.12
threshold of motor
Setting range of P04.03: 0.00Hz–P04.05
Setting range of P04.04: 0.0%–110.0% (of
the rated voltage of motor 1)
Setting range of P04.05: P04.03–P04.07
Setting range of P04.06: 0.0%–110.0% (of
the rated voltage of motor 1)
Setting range of P04.07: P04.05–P02.02
(rated frequency of AM 1) or P04.05–P02.16
(rated frequency of SM 1)
Setting range of P04.08: 0.0%–110.0% (of
the motor rated voltage of motor 1)
The function code is used to compensate
for the motor rotating speed change
caused by load change in the space
voltage vector mode, and thus improve the
rigidity of the mechanical characteristics
of the motor. You need to calculate the
rated slip frequency of the motor as
follows:
-n*p/60
△f=f
b
Of which, f
1, corresponding to function code P02.02. n
is the rated rotating speed of motor 1,
corresponding to function code P02.03. p is
the number of pole pairs of the motor.
100.0% corresponds to the rated slip
frequency △f of motor 1.
Setting range: 0.0–200.0%
In space voltage vector control mode, the
motor, especially the large-power motor,
may experience current oscillation at
certain frequencies, which may cause
unstable motor running, or even VFD
overcurrent. You can adjust the two
function codes properly to eliminate such
phenomenon.
Setting range of P04.10: 0–100
Setting range of P04.11: 0–100
1
Setting range of P04.12: 0.00Hz–P00.03
(Max. output frequency)
Description
is the rated frequency of motor
b
-156-
Function parameter list
Default Modify
0.0%
10
10
30.00Hz