Drive K320 series
®
Function
Name
code
P01.23
Start delay
P01.24
Stop speed delay 0.0–600.0s
Open-loop 0Hz
P01.25
output selection
DEC time for
P01.26
emergency stop
Time of ending
segment of DEC S
curve
P01.27
Time of starting
segment of DEC S
curve
Time of ending
P01.28
segment of DEC S
curve
Short-circuit
P01.29
braking current
Hold time of
P01.30
short-circuit
braking for start
Hold time of
P01.31
short-circuit
braking for stop
Pre-exciting time
P01.32
of jog
Description
After a VFD running command is given,
the VFD is in standby state and restarts
with the delay defined by P01.23 to
implement brake release.
Setting range: 0.0–600.0s
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for
stop
0.0–60.0s
0.0–50.0s
0.0–50.0s
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
enter short-circuit braking.
During stop, if the running frequency of
VFD is lower than the starting frequency
P01.09 of brake for stop, set P01.31 to a
non-zero value to enter short-circuit
braking for stop, and then carry out DC
braking in the time set by P01.12. (Refer to
the descriptions for P01.09–P01.12.)
Setting range of P01.29: 0.0–100.0% (VFD)
Setting range of P01.30: 0.0–50.00s
Setting range of P01.31: 0.0–50.00s
0–10.000s
-143-
Function parameter list
Default Modify
0.0s
0.0s
0
2.0s
0.1s
0.1s
0.0%
0.00s
0.00s
0.000s