Nortel DMS-100 Series Maintenance Manual page 542

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

12-194 Star Remote System card replacement procedures
NTTR87
in a STAR
(continued)
22
At the MAP terminal
23
24
25
297-8353-550 Standard 05.01 March 2001
Use the following table to determine the next step in this procedure.
If you replaced an NTTR87 that
housed DS-1 links for the
Star Hub C-side
Star Hub P-side
To test the busied network links from step 9, type
>TST LINK link_no
and press the Enter key.
where
link_no
is the number of the link that was manually busied in step 10.
Note 1: This step must be performed for each manually busied link.
Note 2: To test the other links connected to the STAR, perform this step
for each link until all links are tested.
If TST
passes
fails
To return to service the P-side links, type
>RTS LINK link_no
and press the Enter key.
where
link_no
is the number of the link manually busied in step 10.
Note 1: This step must be performed for each link that is manually busied.
Note 2: To RTS the other links connected to the STAR, perform the
procedures in this step for each link until all links are returned to service.
If RTS
passes
fails
To post the STAR where the NTTR87 card is located, type
>POST STAR site frame unit
and press the Enter key.
Do
step 23
step 27
Do
step 24
step 34
Do
step 25
step 34