Nortel DMS-100 Series Maintenance Manual page 444

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

12-96 Star Remote System card replacement procedures
NTMX81
in a STAR
(continued)
18
Distance to cross connect
Feet
0-133
133-266
266-399
399-533
533-655
Note: S indicates switch number(s). On S1 dip switch (6 position): S1-S3
belong to even port, and S4-S6 belong to odd port.
19
20
21
22
297-8353-550 Standard 05.01 March 2001
Before inserting the replacement card, set the DS-1 switch settings according
to the following table.
Meters
0-41
41-81
81-122
122-163
163-200
Open the locking lever on the replacement packlet.
a
Align the packlet with the slots in the shelf.
b
Carefully slide the packlet into the card slot in the NTTR87 card.
Seat and lock the packlet.
a
Use your fingers or thumbs to push on the upper and lower edges of the
faceplate of the packlet to make sure the packlet is fully seated in the slot.
b
Close the locking lever.
Use the following information to determine the next step in this procedure.
If you entered this procedure
from
alarm clearing procedures
other
Use the following table to determine the next step in this procedure.
If you replaced an NTMX81 that
connects DS-1 links for the
Star Hub C-side
Star Hub P-side
S3/6
S2/5
On
Off
Off
On
Off
On
Off
Off
Off
Off
Do
step 33
step 22
Do
step 23
step 27
S1/4
Off
On
Off
On
Off