Nortel DMS-100 Series Maintenance Manual page 462

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

12-114 Star Remote System card replacement procedures
NTTR60
in a STAR
(continued)
Replacing an NTTR60 card in a STAR
At your current location
1
2
3
At the MAP terminal
4
297-8353-550 Standard 05.01 March 2001
CAUTION
Loss of service
This procedure includes directions to manually busy one or
more peripheral module (PM) units. Since manually busying
a PM unit can cause service degradation, perform this
procedure only if necessary to restore out-of-service
components. Otherwise, carry out this procedure during
periods of low traffic.
Proceed only if you were either directed to this card replacement procedure
from a step in a maintenance procedure, are using the procedure for verifying
or accepting cards, or were directed to this procedure by your maintenance
support group.
Get a replacement card. Make sure the replacement card has the same
product equipment code (PEC), including suffix, as the card that is to be
removed.
If you were directed to this procedure from an alarm clearing procedure in this
manual, go to step 9. Otherwise, continue with step 4.
To post the STAR containing the card to be replaced, type
>MAPCI;MTC;PM;POST STAR site frame unit
and press the Enter key.
where
site
is the name of the site where the STAR is located
frame
is the frame number of the STAR with the faulty card (0 to 511)
unit
is 0 for the STAR
Example of a MAP response: