Nortel DMS-100 Series Maintenance Manual page 318

Star remote system
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

11-52 Star Remote System alarm clearing procedures
PM STAR
minor
(continued)
33
34
35
36
37
297-8353-550 Standard 05.01 March 2001
TUPLE TO BE CHANGED:
REM1 01 0
(0 NT6X54AA NT6X05AA) (1 NT6X54DA NT6X05DA)
(2 NT6X54AA NT6X05AA) (3 NT6X54AA NT6X05AA) (4 NILDRWR)
(5 NT6X54AA NT6X05AA) (6 NT6X54AA NT6X05AA)
(7 NT6X54AA NT6X05AA) (8 NTTR70AA NTTR40AA 14 RLD11DC 2 DS1HUB 20
LAKE9) (9 NT6X54AA NT6X05AA) (10 NT6X54AA NT6X05AA) (11 NT6X54AA
NT6X05AA) (12 NT6X54AA NT6X05AA) (13 NT6X54AA NT6X05AA) (14 NT6X54AA
NT6X05AA) (15 NT6X54AA NT6X05AA) (16 NT6X54AA NT6X05AA) (17 NT6X54AA
NT6X05AA)$
ENTER Y TO CONFIRM, N TO REJECT, OR E TO EDIT.
To respond affirmatively to the confirmation request, type
>Y
and press the Enter key.
To leave table LCMDRINV, type
>QUIT
and press the Enter key.
IfThe alarm
clears
does not clear
To load the RLD, type
>LOADRLD CC
and press the Enter key.
If LOADRLD
passes
fails
To load the inactive RLD bank from the active bank, type
>LOADRLD MATE
and press the Enter key.
If LOADRLD
passes
fails
To load the inactive RLD bank from the CM, type
>LOADRLD CC
Do
step 61
step 26
Do
step 61
step 59
Do
step 61
step 37