11-20 Star Remote System alarm clearing procedures
PM STAR
critical
(continued)
Clearing a PM STAR critical alarm
At the MAP terminal
1
2
3
4
5
6
297-8353-550 Standard 05.01 March 2001
Ensure that the STAR is receiving power.
If an alarm is still audible, silence it by typing
>MAPCI;MTC;SIL;PM
and pressing the Enter key.
CAUTION
Failing to allow sufficient time may cause false alarm indication.
Allow 3 to 5 minutes for the system to clear the alarm before
proceeding to the next step.
Identify the faulty STAR by typing
>DISP STATE CBSY STAR
and pressing the Enter key.
If response indicates
no CBsy STARs
CBsy STARs
Post the STAR with the alarm condition by typing
>POST STAR CBSY
and pressing the Enter key.
Note: Note the name and number of this STAR.
Identify central side (C-side) links to the host PM by typing
>TRNSL C
and pressing the Enter key.
Example of a MAP response:
Link 0: LTC 0
2; Cap MS; Status: SysB
Link 1: LTC 0
6; Cap MS; Status: SysB
Post the host LTC by typing
>POST LTC ltc_no
and pressing the Enter key.
where
Do
step 14
step 4
;MsgCond: CLS
;MsgCond: CLS