Connecting Data And Supply Cables; Notes - WAGO -SPEEDWAY 767 Manual

8do 24v dc 2.0a if (4xm12) digital output module 24 v dc / 2.0 a
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

40

Connecting Data and Supply Cables

Pos : 23.1 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/I/O-Modul e/01_Ansc hl uss der Daten- und Vers orgungs kabel - Übersc hrift 1 @ 8\mod_1278310189976_21.doc x @ 58919 @ 1 @ 1
5
Connecting Data and Supply Cables
Pos : 23.2 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/I/O-Modul e/02_Hinweis e - Ü bers chrift 2 @ 8\mod_1278310190960_21.doc x @ 58923 @ 2 @ 1
5.1

Notes

Pos : 23.3 /Serie 767 (WAGO-SPEED WAY)/Wic htige Erläuterungen/Sicherheits hinweis e/Gefahr/Gefahr: El ektrisc he Spannung @ 8\mod_1278307980373_21.doc x @ 58901 @ @ 1
Electric voltage!
Operate the 767 Series components exclusively with 24 VDC PELV (Protective
Extra Low Voltage) or SELV (Safety Extra Low Voltage) voltage sources. Failure
to comply may result in electric shock.
Pos : 23.4 /Serie 767 (WAGO-SPEED WAY)/Wic htige Erläuterungen/Sicherheits hinweis e/Achtung/Achtung: H öc hste Strombelastbar keit der Vers orgungs kontakte @ 8\mod_1278308653219_21.doc x @ 58916 @ @ 1
The highest current carrying capacity of the supply contacts is 4 A!
Always observe the maximum current carrying capacity per supply line (U
for each 767 Series component and the overall power consumption for all
767 components. Neither of these values shall exceed 4 A since an increase in
current causes the contacts to overheat and damages the 767 Series components.
Information regarding the power demand of each 767 Series component can be
found in the corresponding data sheet, which is available from www.wago.com.
Pos : 23.5 /Serie 767 (WAGO-SPEED WAY)/Wic htige Erläuterungen/Sicherheits hinweis e/Achtung/Achtung: Offene Ansc hlüss e @ 8\mod_1278308159953_21.doc x @ 58910 @ @ 1
Exposed connections!
If connections have not been closed with protective caps, liquid or dirt can
penetrate the components of the 767 Series module and ruin it. Therefore, close
all unnecessary connections with protective caps, which must be ordered
separately, in order to maintain the IP67 degree of protection. (See section
"Accessories" of the fieldbus coupler/controller manual.)
Pos : 23.6 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/I/O-Modul e/Ans chl uss _Hinweise allgemeiner T eil 1 @ 5\mod_1249286391531_21.doc x @ 39858 @ @ 1
The connectors must be disconnected from the power supply when screws
are tightened.
Tighten the connectors by hand. To achieve the required torque (see below)
for the connector, use the torque wrench with the order number 206-701.
Torque for M8 connectors:
Torque for M12 connectors:
Pos : 23.7 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/I/O-Modul e/Ans chl uss _Hinweise allgemeiner T eil 2 @ 5\mod_1249298321031_21.doc x @ 40028 @ @ 1
Use torque wrench 206-701!
Only use the specified torque wrench. Using mechanical tools can cause the
threads to strip.
In this case, replace the module!
Pos : 23.8 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/I/O-Modul e/Ans chl uss _Hinweise T eil 3 @ 5\mod_1249287289312_21.doc x @ 39865 @ @ 1
For both power supply and S-BUS, use only pre-assembled WAGO system
cables so the specified characteristics of the technical data can be achieved.
767-4804/000-800 8DO 24V DC 2.0A IF (4xM12)