8.1

Connecting Client PC and Fieldbus Nodes

1. Mount the fieldbus node on the TS 35 carrier rail.
Follow the mounting instructions found in the "Mounting" chapter.
2. Connect the 24 V power supply to the supply terminals.
3. Connect the PC's ETHERNET interface to the head station's ETHERNET
interface (RJ-45) of your fieldbus node.
4. Turn the operating voltage on.
The head station is initialized. The head station determines the I/O module
configuration of the fieldbus node and creates a process image.
During start-up, the I/O LED (red) flashes.
If the I/O LED lights up green after a brief period, the fieldbus node is operational.
If an error has occurred during initialization, it is red flashed with an error code by
the I/O LED.
If the I/O LED flashes 6 times (indicating error code 6) and then 4 times
(indicating error argument 4), this indicates that an IP address has not been
assigned yet.
8.2

Determining the IP Address of the PC

To determine the IP address of the PC (with Microsoft Windows operating
system) using the MS DOS prompt, proceed as follows:
1.
Go via "Start"> "Search programs/files".
2.
Enter the command "cmd" in the input field.
3.
Choose at
(Windows 7): "cmd.exe" and
(Windows 10): "Command Prompt".
Press [Enter] key to confirm the entry.
4.
The MS DOS prompt window opens.
5.
In the MS DOS prompt window enter the command "ipconfig".
6.
Press [Enter] key to confirm the entry.
The IP address, subnet mask and the default gateway with the corresponding
parameters of the PC are displayed.