Power Jumper Contacts/Field Supply; Figure 3: Power Jumper Contacts; Table 4: Legend For Figure "Power Jumper Contacts - WAGO 750-1605/040-000 Manual

Potential distribution 16*24v xtr 16-way 24 v; extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-1605/040-000 Potential Distribution 16*24V XTR
3.2.2

Power Jumper Contacts/Field Supply

Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
The I/O module 750-1605/040-000 has 2 self-cleaning power jumper contacts
that supply and transmit power for the field side. The contacts on the left side of
the I/O module are designed as blade contacts and those on the right side as
spring contacts.

Figure 3: Power Jumper Contacts

Table 4: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Type
Function
Spring contact Potential transmission (U
Spring contact Potential transmission (0 V) for field supply
Blade contact
Potential feed-in (0 V) for field supply
Blade contact
Potential feed-in (U
Device Description
) for field supply
v
) for field supply
v