8. Disconnect the wires from the AC terminal block on the three-phase wye AC PDM (see
Figure 196 on page
448), loosen each of the input terminals or grounding point screws, and remove
each wire from the grounding point or input terminal.
To remove wires from the terminal block that serves six PSMs:
a. Remove the wire labeled N from the input terminal labeled N1.
b. Remove the wire labeled L3 from the input terminal labeled C1.
c. Remove the wire labeled L2 from the input terminal labeled B1.
d. Remove the wire labeled L1 from the input terminal labeled A1.
e. Remove the grounding wire from the grounding point labeled GND.
Figure 196: Disconnecting the Power Cord from a Three-Phase Wye AC Power Distribution Module
To remove wires from the terminal block that serves three PSMs:
a. Remove the wire labeled N from the input terminal labeled N2.
b. Remove the wire labeled L3 from the input terminal labeled C2.
c. Remove the wire labeled L2 from the input terminal labeled B2.
448