Hide thumbs Also See for MX2008:
Table of Contents

Advertisement

3. Plug the power cord into the power sockets on the DC PDM (240 V China). Refer to Figure 1. Press
the latch on the side of the power cable before pushing it in. Apply slight pressure so that the power
cord is firmly seated in the power socket until you feel it engage. As you plug in each power cord, the
power LED for the socket lights up green.
Figure 137: Connecting Power
4. Connect the power cords for the remaining PDMs.
5. Connect the power cable (CBL-PWR-240V-CH) to the DC power source. See
Figure 139: 240 V China Power Cable
1
Negative
2
Ground
6. Switch on the dedicated customer site circuit breaker.
7. On each of the DC power input sources, switch the DC circuit breaker to the center position before
moving it to the ON position.
1
2
3
3
Positive
Figure 139 on page
334.