NOTE:
The MX2008 supports 4-AWG DC power cable lugs for 80-A input (see
Figure 65 on page
205), and 6-AWG DC power cable lugs for 60-A input (see
Figure 65: 4-AWG DC Power Cable Lugs for 80-A Input
End view
0.27
0.55
2 holes
0.09
0.25
0.63
Figure 66: 6-AWG DC Power Cable Lugs for 60-A Input
End view
.48 ±.04
.25 ±.04
Table 87 on page 205
summarizes the specifications for the power cables, which you must supply.
Table 87: DC Power Cable Specifications
Cable Type
Quantity and Specification
Power
Eighteen pairs of 4-AWG (21.2 mm
90°C wire, or as required by the local code.
Power
Eighteen pairs of 6-AWG (13.3 mm
90°C wire, or as required by the local code.
MX2008 Router Grounding Cable Specifications
The 48 VDC facility must be equipped with a circuit breaker rated 60 A (–48 VDC), or 80 A (–48 VDC) for
each PDM input, and the grounding cable must be minimum 10 AWG, or as required by the local code.
Inner diameter .28
All measurements in inches
Inner diameter .22
0.63 ±.02
.27 ±.02
2 PLC
All measurements in inches
2
2
), used with 80-A PDM. Minimum
), used with 80-A PDM. Minimum
Figure 66 on page
205).
205