No.
Name
Bi-Directional Speed
b3-14
Search Selection
Speed Search Restart
b3-17
Current Level
Speed Search Restart
b3-18
Detection Time
Number of Speed
b3-19
Search Restarts
Speed Search Method
b3-24
Selection
Speed Search Retry
b3-25
Interval Time
Timer Function
b4-01
On-Delay Time
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
This parameter enables the drive to detect
motor direction during speed search.
0: Disabled–Drive uses frequency reference
direction.
1: Enabled–Drive uses detected direction.
Sets the speed search restart operation detection
current level in percentage units. The drive's
rated current is set at 100%
Sets the time in seconds for speed search restart
to be detected.
Sets the number of restarts possible for speed
search restart operations.
Sets the speed search method used at start-up
and after a momentary power loss.
0: Current Detection Type
1: Speed Estimation Type
Parameter b3-01 enables this function at start,
and parameter L2-01 enables this function
during momentary power loss.
Current Detection Type - Start speed search
from max frequency or from the frequency
when momentary power loss occurred. Detects
motor speed based on the current level
(conventional method).
Speed Estimation Type - Estimates the motor
speed when speed search begins. Accelerates or
decelerates to the estimated frequency. Works
in both forward and reverse.
Sets waiting time until the search retry
operation beginning when searching for the
speed of PM in 0.1 seconds.
b4: Timer Function
Use b4 parameters to configure timer function operation.
Used in conjunction with a multi-function
digital input (H1-
= 18) and a multi-
function digital output (H2-
programmed for the timer function. This sets
the amount of time between digital input
closure and digital output activation.
B.2 Parameter Table
Range Def.
0,1
0
150
0 to 200
%
0.00 to
0.10
1.00
s
0 to 10
3
0,1
0
0 to 30.0 0.5 s A A A 1C8
= 12)
0.0 to
0.0 s A A A 1A3
300.0
Control
Mode
Addr.
Pg.
V/f O
P
Hex
LV
M
A A −
19E
A A −
1F0
A A −
1F1
A A −
1F2
A A − 1C0
B
339

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents