◆
Details on Terminal Board (TB) or Control Board (CNT)
Replacement
The drive Terminal Board retains drive parameter settings to significantly improve
the ease of drive replacement. Refer to
board replacement. When replacing the drive, or changing the Control Board or
Terminal Board, the following error codes may be encountered upon application of
power:
• oPE04 Drive parameter settings need to be initialized or uploaded from the TB.
• CPF06 Drive specification does not match the replaced drive.
• oPE01 Drive parameter o2-04 kVA requires setting.
Procedural Notes:
1. When replacing the drive, control board or terminal board, make sure to confirm
the kVA setting, parameter o2-04 is correct upon initial power-up.
2. Next perform an initialization, (via parameter A1-03) to obtain the desired
parameter settings.
3. In cases where a previously programmed terminal board is retained, initializing
the drive with a setting of A1-03 = 5550 may be desired to program the drive with
previously programmed settings (settings used prior to replacing the drive or
control board).
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
6.5 Drive Replacement
Figure 6.13
for a flowchart to assist in
6
287