b: Application

Application parameters configure the Run Command Source, DC Injection
Braking, Speed Search, Timer functions, PID control, the Dwell function, Energy
Savings and a variety of other application-related settings.
No.
Name
Frequency Reference
b1-01
Selection 1
Run Command
b1-02
Selection 1
Stopping Method
b1-03
Selection
Reverse Operation
b1-04
Selection
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
Selects the frequency reference input source.
0: Operator - Digital preset speed U1-01 or
d1-01 to d1-17.
1: Terminals - Analog input terminal A1 (or
terminal A2 based on parameter H3-09).
2: Serial Com - Modbus RS-422/485 terminals
R+, R-, S+ and S-.
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Operator - RUN and STOP keys on the
digital operator.
1: Terminals - Contact closure on terminals S1
or S2.
2: Serial Com - Modbus RS-422/485 terminals
R+, R-, S+ and S-.
3: Option PCB.
Selects the stopping method when the run
command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection Braking to Stop
3: Coast with Timer (A new run command is
ignored if received before the timer expires)
Sets the forward rotation of the motor, and if
reverse operation is disabled.
0: Reverse enabled.
1: Reverse disabled.
B.2 Parameter Table
Control
Mode
Range Def.
Addr.
O
P
Hex
V/f
LV
M
0 to 4
1
S S S
180
0 to 3
1
S S S
181
0 to 3
0
S S S
182
DC Injection Braking at Stop
cannot be selected when using
Open Loop Vector for PM motors.
0,1
0
A A A 183
Pg.
130
133
B
136
335