YASKAWA V1000 Series Installation & Start-Up Manual page 337

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
DC Injection Braking
b2-01
Start Frequency
DC Injection Braking
b2-02
Current
DC Injection Braking
b2-03
Time/DC Excitation
Time at Start
DC Injection Braking
b2-04
Time at Stop
Magnetic Flux
b2-08
Compensation
Capacity
Short Circuit Brake
b2-12
Time at Start
Short Circuit Brake
b2-13
Time at Stop
DC Injection Braking
b2-15
Current 2
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
Sets the frequency at which DC Injection
Braking starts when Ramp to Stop (b1-03 = 0)
is selected. If b2-01< E1-09, DC Injection
Braking starts at E1-09.
Sets the DC Injection Braking current as a
percentage of the drive rated current.
Sets the time of DC Injection Braking at start in
units of 0.01 seconds. Disabled when set to 0.00
seconds.
Used to stop a coasting motor.
Sets the time length of DC Injection Braking at
stop in units of 0.01 seconds.
When b1-03 = 2, actual DC Injection time is
calculated as follows:
(b2-04) x 10 x (Output Freq) / (E1-04).
When b1-03 = 0, this parameter sets the amount
of DC Injection time applied to the motor at the
end of the decel ramp.
This should be set to a minimum of 0.50
seconds when using HSB. This will activate DC
Injection during the final portion of HSB and
help ensure that the motor stops completely.
Disabled when set to 0.00.
Sets the magnetic flux compensation as a
percentage of the no-load current value
(E2-03).
Sets the time for Short-Circuit Brake operation
at start in units of 0.01 seconds. Used when
restarting a coasting motor once it has stopped.
Disabled when set to 0.00.
Sets the time for Short-Circuit Brake operation
at stop in units of 0.01 seconds. Used to stop a
motor rotating due to inertia. Disabled when set
to 0.00 seconds.
<32>
Changes the DC Injection Braking reference
one second after start. Disabled when set to
0.0%.
B.2 Parameter Table
Range Def.
0.0 to
10.0
0 to 75 50% A A − 18A
0.00 to
10.00
0.00 to
10.00
0 to
1000
0.00 to
25.50
<32>
0.00 to
25.50
0 to 100 50% A A − 01BD —
Control
Mode
Addr.
Pg.
V/f O
P
Hex
LV
M
0.5
A A A 189
Hz
0.00
A A − 18B
s
<1>
0.50
A A − 18C
s
<14>
0% − A −
190
0.00
− − A 1BA —
s
0.50
− − A 1BB
s
337