Wiring the Main Circuit Terminal
WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the
main circuit terminals. Failure to comply may result in death or serious injury.
Note: 1. A protective cover is placed over option-related terminals prior to shipment.
Use a pair of needle-nose pliers to remove the protective cover.
2. The protective cover is held in place by the ground terminal screw on NEMA Type 1
models.
Main Circuit Connection Diagram
Figure 3.16
and
Figure 3.17
Connections may vary based on drive capacity.
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not
connect braking resistors to any other terminals. Improper wiring connections could result in
death or serious injury by fire. Failure to comply may result in damage to the braking circuit or
drive.
Single-Phase 200 V Class (CIMR-V BA0001 to 0012)
Figure 3.16
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
A
A – Protective Terminal Cover
illustrate the standard drive connection diagrams.
DC reactor
(option)
Jumper
2
1
R/L1
S/L2
Single-phase
200 Vac
Figure 3.16 Connecting Main Circuit Terminals
3.6 Main Circuit Wiring
Braking Resistor
Unit (option)
B1 B2
Drive
U/T1
V/T2
Motor
W/T3
3
73