YASKAWA V1000 Series Installation & Start-Up Manual page 215

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Cause
Motor has overheated.
Motor has overheated.
Motor has overheated.
LED Operator Display
Cause
Load is too heavy.
Cycle times are too short during
acceleration and deceleration.
• The drive is overloaded at low
speeds.
• Overload may occur at low speeds
when using a general-purpose
motor, even if operating within the
rated current limitation.
Although a special type of motor is
being used, the motor protection
selection is set for a general-purpose
motor (L1-01 = 1).
Voltage is too high for the V/f
characteristics.
The wrong motor-rated current is set
to E2-01.
The maximum frequency for the
drive input power is set too low.
Multiple motors are running off the
same drive.
The electrical thermal protection
characteristics and motor overload
characteristics do not match.
The electrical thermal relay is
operating at the wrong level.
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
• Check the size of the load, the accel/decel times and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve
reducing E1-08 and E1-10.
Be careful not to lower E1-08 and E1-10 excessively because this reduces
load tolerance at low speeds.
• Check the motor-rated current.
• Enter the motor-rated current as indicated on the motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
Motor Overload
oL1
The electrothermal sensor tripped overload protection.
Reduce the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
• Reduce the load.
• Increase the speed.
• If the drive is supposed to operate at low speeds, either increase the motor
capacity or use a motor specifically designed to operate with the drive.
Set L1-01 = "2".
• Adjust the user set V/f patterns (E1-04 through E1-10). Parameters E1-08 and
E1-10 may need to be reduced.
• If E1-08 and E1-10 are set too high, there may be very little load tolerance at
low speed.
• Check the motor-rated current.
• Enter the value written on the motor nameplate to parameter E2-01.
• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).
Disable the Motor Protection function (L1-01 = "0") and install a thermal relay
to each motor.
• Check the motor characteristics.
• Correct the value set to L1-01 (Motor Protection Function).
• Install an external thermal relay.
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor-rated current (E2-01).
5.5 Fault Detection
Possible Solution
Fault Name
Possible Solution
5
215

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents