4.4 Basic Parameter Adjustments

4.4
Basic Parameter Adjustments
This section explains the basic settings required for initial drive operation.
Checking these basic parameter settings during start-up will help to ensure a
successful drive start-up.
If more information is required for parameters not listed in this section,
Parameter List on page 331

Control Mode Selection

Available Control Modes
Three motor control modes are available. Select the control mode that best suits the
application in which the drive will be used.
Control Mode
V/f Control
Open Loop Vector Control
PM Open Loop Vector Control

Initialize Parameter Values: A1-03

Parameter A1-03 (Initialize Parameters) resets all parameters to the original default
values.
Note: Be sure to save all changed parameter settings by setting o2-03="1" before
initializing the drive. Your settings will be lost if a 2-wire or 3-wire initialization
using 2220, or 3330 if performed without first saving user parameters.
Back-up of Parameter Values: o2-03 on page
124
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
as required for a complete listing of drive parameters.
Parameter
• General variable speed applications, particularly useful for
A1-02 = 0
running multiple motors from a single drive
(default)
• When replacing a drive in which parameter settings are
unknown.
• General variable speed applications
A1-02 = 2
• Applications requiring high precision, high speed control.
Variable torque applications employing permanent magnet motors
A1-02 = 5
and energy savings.
Main Applications
173.
refer to