B.2 Parameter Table
No.
Name
Stopping Method
H5-04
After Communication
Error
Communication Fault
H5-05
Detection Selection
Drive Transmit Wait
H5-06
Time
RTS Control
H5-07
Selection
H5-09
CE Detection Time
Unit Selection for
H5-10
MEMOBUS/Modbus
Register 0025H
Communications
H5-11
ENTER Function
Selection
Run Command
H5-12
Method Selection
380
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
Selects the stopping method when a
communication time-out fault (CE) is detected.
0: Ramp to stop
1: Coast to stop
2: Fast-stop
3: Alarm only
Enables or disables the communications time-
out fault (CE).
0: Disabled - A communication loss will not
cause a communication fault.
1: Enabled - If communication is lost for more
than two seconds, a CE fault will occur.
Set the delay time from when the drive
receives data to when the drive sends data.
Enables or disables "request to send" (RTS)
control:
0: Disabled - RTS is always on.
1: Enabled - RTS turns on only when sending.
Sets the time required to detect a
communications error. Adjustment may be
need when networking several drives.
Selects the units used for MEMOBUS/Modbus
registry 0025H (Output Voltage Reference
Monitor).
0: 0.1 V units
1: 1 V units
Select the function for the enter command that
saves parameter data to the drive.
0: Save parameter data that was edited to the
drive when the enter command is given.
1: Parameter data that has been edited is saved
when the enter command is given (compatible
with the V7).
0: FWD/STOP, REV/STOP Method
1: RUN/STOP, FWD/REV Method
Control
Mode
Range Def.
O
V/
P
L
f
M
V
0 to 3
3
A A A
0,1
1
A A A
5 to 65 5 ms A A A 42A
0,1
1
A A A 42B
0.0 to
2.0 s A A A
10.0 s
0, 1
0
A A A
0, 1
1
A A A 43C
0, 1
0
A A A 43D
Addr.
Pg.
Hex
428