A.5 Drive Derating Data
A.5

Drive Derating Data

The drive can be operated at above rated temperature, altitude and default carrier
frequency by derating the drive capacity. For example, a 10 amp continuous rated
drive may be operated at higher temperatures if it is only used to supply 8 amps
continuous.

Carrier Frequency Derating

As the carrier frequency of the drive is increased above the factory setting the drive
capacity should be derated according to
Figure A.1
200 V Class:
80% of HD
400 V Class
60% of HD

Temperature Derating

As the ambient temperature for the drive is increased above the drive specification
the drive should be derated. Additionally parameter L8-35 Side-by-Side Selection
on page
395
should be set according to enclosure type and mounting method as
illustrated in
Figure A.2 Ambient Temperature and Installation Method Derating
on page
329.
328
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Drive
Carrier Frequency Derating
Rating
Carrier(C6-02)
Figure A.1 Carrier Frequency Derating
Figure
A.1.