YASKAWA V1000 Series Installation & Start-Up Manual page 372

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

B.2 Parameter Table
H1-
Function
Setting
Run Command (2-wire
42
sequence 2)
FWD/REV Command (2-wire
43
sequence 2)
44
Offset Frequency 1 Addition
45
Offset Frequency 2 Addition
46
Offset Frequency 3 Addition
DC Injection Braking
60
Command
61
External Search Command 1
62
External Search Command 2
65
KEB Ride-Thru (N.C.)
66
KEB Ride-Thru (N.O.)
67
Communications Test Mode
68
High-Slip Braking
6A
Drive Enable
75
Up 2 Command
76
Down 2 Command
7A
KEB Ride-Thru 2 (N.C.)
372
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
H1 Multi-Function Digital Input Selections
Open: Stop
Closed: Run
Note: Settings 40 and 41 cannot be utilized at the same
time.
Open: Reverse
Closed: Forward
Note: Settings 40 and 41 cannot be utilized at the same
time.
Closed: Add to the main frequency reference.
This function is used with offset frequency 1 (d7-01)
Closed: Add to the main frequency reference. (d7-02)
Closed: Add to the main frequency reference. (d7-03)
Closed: Triggers DC Injection Braking (b2-02)
Closed: Executes Speed Search from the maximum
output frequency (E1-04). Based on the b3-01 (Speed
Search at Start).
Closed: Executes Speed Search from the frequency
reference. Based on the b3-01 (Speed Search at Start).
Open: KEB Ride-Thru enabled.
Closed: Normal operation.
Closed: Enables KEB Ride-Thru.
Tests the MEMOBUS/Modbus RS-485/422 interface.
Displays, "Pass" if the communication test is successful.
Closed: High-Slip braking is executed regardless of the
current command and the drive stops.
Open: Drive is disabled. If this contact is opened during
run, then the drive will stop as specified by parameter
b1-03.
Closed: Run command can be entered.
Open: Maintains the current frequency reference
Closed: Increases or decreases the frequency reference.
UP 2 and Down 2 commands must be set in combination
with each other. The source of the frequency reference
must also be assigned to the control terminals
(b1-01 = "1").
Open: KEB deceleration at momentary power loss
command 2 (N.C. contact)
Description
Control
Mode
Pg.
V/
O
P
f
LV
M
O O O —
O O O —
O O O —
O O O —
O O O —
O O -
O O O —
O O O —
O O O —
O O O —
O O O —
O -
-
O O O —
O O O —
O O O —
O O O —

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents