YASKAWA V1000 Series Installation & Start-Up Manual page 365

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

No.
Name
Motor d Axis
E5-06
Inductance
Sets the d axis inductance in units of
(for PM
0.01 mH.
<25>
motor)
Motor q Axis
E5-07
Inductance
Sets the q axis inductance in units of
(for PM
0.01 mH.
<25>
motor)
Set the inductance voltage for each motor
phase in units of 0.1 mV (rad/min) [electrical
angle]. Note: (Yaskawa PM motors not
Motor
marketed in the U.S.)
Induction
Set this parameter when using a Yaskawa
E5-09
Voltage
SSR1 series PM motor with derate torque, or
<25>
Constant 1 (for
a Yaskawa SST4 series motor with constant
PM motor)
torque. When setting this parameter, E5-24
should be set to 0. An alarm will be triggered
if both E5-09 and E5-24 are set to 0, or if
neither parameter is set to 0.
Set the inductance voltage for each motor
phase in units of 0.1 mV/(r/min) [mechanical
angle] Note: (Yaskawa PM motors not
Motor
marketed in the U.S.) Set this parameter when
Induction
using a Yaskawa SMRA series pico motor.
E5-24
Voltage
When setting this parameter, E5-09 should be
Parameter 2
set to 0. An alarm will be triggered if both E5-
<25>
(for PM
09 and E5-24 are set to 0, or if neither
motor)
parameter is set to 0. If E5-03 (Motor Rated
Current) is set to 0, however, then an alarm
will not be triggered when both E5-09 and
E5-24 are set to 0.
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for
A1-02 = 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for
A1-02 = 0-V/f Control.
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-
06 does not = 0.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
<17> Default setting value is dependent on parameter o2-04, Drive Capacity, when parameter H1-
selected as a digital input. The value shown is when o2-04 = 98 (62H) 200V class 0.4 kW drive.
<20> Range upper limit is dependent on parameters E5-01, Motor Code Selection, and A1-02, Control Method
Selection. The value shown is for A1-02 = 5-PM OLV control.
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
B.2 Parameter Table
Control
Mode
Range
Def.
O
P
V/f
L
M
V
0.00 to
S
<10>
300.00
0.00 to
S
<10>
600.00
0.0 to
S
<10>
2000.0
0.0 to
0
S
2000.0
<10>
Addr.
Pg.
Hex
32E
122
32F
122
331
122
353
122
B
= 16 Motor 2 is
365