4.4 Basic Parameter Adjustments
L1-01
Motor
Setting
Type
Inverter
2
Duty motor
(10:1)
Vector
3
motor
(1000:1)
Notes on Motor Protection
• Motor protection meeting UL and cUL standards has been achieved with the
motor overload protection time (L1-02) set to factory default setting. Therefore,
this parameter does not normally need to be changed. In the event the motor
overload characteristics are known, the overload time can be adjusted to more
closely match the motor. To detect overload more quickly, reduce L1-02.
158
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Overload Tolerance
150
Rated Speed = 100% Speed
60 seconds
100
(%)
55
50
Continuous
A
0 1 10
100
120
(60Hz)
Speed
(%)
150
Rated Speed = 100% Speed
60 seconds
100
90
(%)
50
A
Continuous
0 1
100
120
167
(60Hz)
Speed
(%)
A: Typical maximum speed for Yaskawa motor frame number 200LJ and greater
B: Typical maximum speed for Yaskawa motor frame numbers 160MJ – 180LJ
C: Typical maximum speed for Yaskawa motor frame number 132MHJ or less
D: Typical maximum speed for Yaskawa motor frame number 132MJ or less
Cooling Fan Capacity
Motor designed for
effective cooling above
6 Hz.
B
D
167
200
Motor capable of
effective cooling at
extremely low speeds
(0.6 Hz).
B
D
200
Electrothermal
Protection
(100% motor
overload)
Continuous operation
between 6 and 60 Hz.
Continuous operation
between 0 and 60 Hz.

Hide quick links: