B.2 Parameter Table
No.
Name
b5-20 PID Setpoint Scaling
b5-34
PID Output Lower
Limit
<22>
b5-35
PID Input Limit
<22>
PID Feedback High
b5-36
Detection Level
PID Feedback High
b5-37
Level Detection Time
PID Setpoint / User
b5-38
Display
PID Setpoint and
b5-39
Display Digits
342
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
Sets the units for b5-19, and for parameter
monitors U5-01 (PID Feedback) and U5-04
(PID Setpoint).
0: 0.01Hz units
1: 0.01% units
(100% of max output frequency)
2: r/min (check the number of motor poles)
3: User-set (set to b5-38 and b5-39)
Sets the minimum output possible from the PID
controller. Set as a percentage (%) of the
maximum frequency. When set to 0.0%, lower
limit is disabled.
Limits the input (error signal) to the PID
controller. Set as a percentage (%) of maximum
frequency. Acts as a bipolar limit.
Sets the PID feedback high detection level as a
percentage (%) of the maximum frequency (E1-
04).
Sets the PID feedback high level detection
delay time in seconds.
0 to 60000: User-Set Display
Set the numbers displayed by designating the
maximum output frequency.
Sets the number of digits for setting and
displaying the PID setpoint.
0: Integer
1: One decimal places
2: Two decimal places
3: Three decimal places
Control
Mode
Range Def.
V/f O
P
LV
M
0 to 3
1
A A A 1E2
-100.0 to
0.00
A A A 19F
+100.0
%
0 to
1000.
A A A 1A0
1000.0
0%
100
0 to 100
A A A 1A1
%
0.0 to
1.0 s A A A 1A2
25.5
1 to
A A A 1FE
<5>
60000
0 to 3
A A A 1FF
<5>
Addr.
Pg.
Hex