B.2 Parameter Table
H2-
Function
Setting
0
During Run
1
Zero Speed
2
Fref/Fout Agree 1
3
Fref/Fset Agree 1
Frequency (FOUT)
4
Detection 1
Frequency (FOUT)
5
Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock
9
Option Reference
A
Local/Remote
Torque Detection 1
B
(N.O.)
C
Loss of Reference
D
Braking Resistor Fault
E
Fault
F
Not used
10
Alarm
Reset Command
11
Active
374
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
H2 Multi-Function Digital Output Settings
Closed: There is a run command present or the drive is outputting
voltage.
Closed: Output frequency is 0.
Closed: Output frequency equals the speed reference (plus or
minus the value set to L4-02).
Closed: Output frequency and speed reference equal the value in
L4-01 (plus or minus the hysteresis of L4-02).
Closed: Output frequency is less than or equal to the value in
L4-01 with hysteresis determined by L4-02.
Closed: Output frequency is greater than or equal to the value in
L4-01, with hysteresis determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state,
and in the Drive mode.
Closed: DC bus voltage is below the UV trip level set in L2-05.
Closed: This is no output voltage
Closed: Digital operator supplies the frequency reference.
Closed: Digital operator supplies the run command.
Closed: Output current/torque exceeds the torque value set in
parameter L6-02 for longer than the time specified in parameter
L6-03.
Closed: Drive detects a loss of the analog frequency reference.
Frequency reference is considered lost when it drops 90% in 0.4
seconds. Enabled when L4-05 = 1 (instructing the drive to take
action when the frequency reference is lost).
Closed: Braking resistor or transistor is overheated or faulted out.
This selection requires that braking resistor protection parameter
be set for ERF (L8-01 = "1").
Closed: Fault situation is present.
A fault has occurred (other than CPF00 and CPF01).
Not used:
Set this value when the terminal is not used, or when using the
terminal in the pass-through mode.
Closed: An alarm is triggered.
Example: 90% of the IGBT maintenance period has passed.
Closed: When the drive receives a reset command from a digital
input terminal or serial communication.
Description
Control
Mode
Pg.
O
V/
P
L
f
M
V
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —
O O O —