3.7 Control Circuit Wiring
Figure 3.22
A
A – Drive side
B – Shield
C – Insulation
Figure 3.22 Preparing the Ends of Shielded Twisted-Pair Cables
2.
Ensure that the terminal board is fastened back into place after wiring is
complete.
tightening torque specifications.
3.
Use a multimeter to check for wiring mistakes.
Use shielded twisted-pair wires for analog signal references. Ground the shield of
twisted-pair wires to the ground terminal of the drive.
NOTICE: The analog signal lines between the drive and the operator station or peripheral
equipment should not exceed 50 meters when using an analog signal from a remote source to
supply the frequency reference. Failure to comply could result in poor system performance.
82
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
B
F
Refer to Wire Gauges and Tightening Torque on page 69
C
E
D – Control device side
E – Shield sheath
(Insulate with tape)
F – Connect shield to ground
terminal of drive