B.2 Parameter Table
No.
Name
User Parameter
o2-03
Default Value
o2-04
Drive/kVA Selection
Frequency Reference
o2-05
Setting Method
Selection
Operation Selection
when Digital
o2-06
Operator is
Disconnected
Motor Direction at
o2-07
Power Up when
Using Operator
Initialization
Specification
o2-09
Selection
DELETE for U.S.
402
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Description
Allows storing of parameter settings as a User
Initialization Selection.
0: No Change
1: Set Defaults - Saves current parameter
settings as user initialization.
2: Clear All - Clears the currently saved user
initialization.
Sets the kVA of the drive.
This parameter only needs to be set when
installing a new control board. Do not change
for other reason.
Sets the function of the Data/Enter key.
0: Disabled - Data/Enter key must be pressed
to enter a frequency reference.
1: Enabled - Data/Enter key is not required.
The frequency reference is adjusted by the
"up" and "down" arrow keys on the digital
operator without having to press the ENTER
key.
Sets drive action when the digital operator is
removed in Local mode or with b1-02 = 0.
0: Disabled - The drive will not stop when the
digital operator is removed.
1: Enabled - The drive will fault (OPR) and
coast to stop when the digital operator is
removed.
0: Forward
1: Reverse
This parameter requires that drive operation be
assigned to the digital operator.
Sets parameter default values after a drive
initialization (A1-03) is executed.
1: American specification
2: European specification
3: China specification
Control
Mode
Range Def.
O
V/
P
L
f
M
V
0 to 2
0
A A A 507
0 to FF
A A A 508
<12>
0,1
0
A A A 509
0,1
A A A 50A
<14>
0 to 1
0
A A A 527
A
A
A
0 to 4
0
F
F
F
Addr.
Pg.
Hex
50D