YASKAWA V1000 Series Installation & Start-Up Manual page 323

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Altitude
Ambient Operating
Temperature
Enclosure Types
Humidity
Oil Tolerance
Fire Resistance
Hazardous Materials
Input Voltage Specifications
Input Noise Tolerance
Input Frequency
Electromagnetic Immunity
Leakage Current
DC Input
Displacement Power Factor
Drive Efficiency
Safety
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Item
~
Degrees C
Location
IP20
NEMA Type 1
%RH
~
~
~
~
~
~
~
~
~
~
%
Insulation Voltage Resistance
Smoke/Fire Production
Heat Generation
Discharge Time
Safety Standards.
Fast-stop
A.3 Common Drive Specifications
Specification
1000 m and below
(output derating of 1% per 100 m above 1000
m)
-10~+40º C (NEMA Type 1)
-10~+50º C (Open-Chassis)
Derating:
NEMA Type 1 +50º C /
Open-Chassis +60º C, 80% derate
NEMA Type 1 +60º C 60% derate
Indoor free from corrosive gases or dust
Standard
Standard
95% RH or less, non-condensing
Option
UL508C
RoHS compliant
Single-Phase 200~240 V 50/60 Hz
Three-Phase 200~240 V 50/60 Hz
Three-Phase 380~480 V 50/60 Hz
-15%, +10%
Impulse noise, switching noise according to
(VES-J5002)
50/60 Hz, +/-5%
Standard: EN61800-3 second environment
(motor length 5 m)
1 mA and less, when ground capacitor switch
is off
Compatible, all models:
200V class models: Input range 270~340 V
400V class models: Input range 510~680 V
0.98
96 to 98
200V Models: 2000V, 1 minute (Main Circuit
Control: 2600 V, 5 s)
400 V Models: 2500 V, 1 minute
(2600 V, 5 s)
Non-smoke producing material
Enclosure Exhaust Temperature 65º C,
Maximum 80 º C or less
5 minutes maximum
Standard
(IEC61508 SIL2, EN954-1 category 3)
Stop Cat.0 (Hardwire BB): standard
Yes
A
323

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents