Main Frequency Reference; Terminal A2 Switch - YASKAWA V1000 Series Installation & Start-Up Manual

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

3.9 Main Frequency Reference

3.9
Main Frequency Reference

Terminal A2 Switch

The main frequency reference can either be a voltage or current signal input. For
voltage signals both analog inputs, A1 and A2, can be used, for current signals A2
must be used.
To use current input at terminal A2, set the DIP switch S1 to "I" (factory setting;
right) and set parameter H3-09 = "2" or "3" (4-20 mA or 0-20 mA). Set parameter
H3-10 = "0" (frequency reference).
Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0
and H3-10 = 0), the addition of both input values builds the frequency reference.
When using input A2 as voltage input, set the DIP switch S1 to "V" (left position)
and program parameter H3-09 accordingly.
Voltage Input
0 to 10 V
2 kΩ
88
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Table 3.10 Frequency Reference Configurations
Drive
+10.5 V
+V
20 mA current
Main speed
frequency reference
A1
(voltage input)
Main speed
A2
frequency reference
(current input)
AC
Frequency reference
common
Current Input
+10.5 V
+V
20 mA current
Main speed
A1
4 to 20 mA input
frequency reference
(voltage input)
or
Main speed
0 to 20 mA input
A2
frequency reference
(current input)
AC
Frequency reference
common
Drive

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents